Common OPC UA Server Test Report

We use the following common OPC UA Server and test the communication between it and the OPC UA driver in WAGO SCADA.

OPC UA Server

  1. Prosys: v5.5.0-341
  2. Softing: v1.46.0.7478
  3. Matrikon: v1.9.0.8629

Test Results

1. Supports connectivity via secure connections

Authentication Secured Connection
Prosys Y Y
Softing Y Y
Matrikon Y Y

2. WAGO SCADA supports the following data types for OPC UA Server

Prosys Softing Matrikon
Byte R/W R/W R/W
SByte R/W R/W R/W
Int16 R/W R/W R/W
Int32 R/W R/W R/W
Int64 R/W R/W R/W
UInt16 R/W R/W R/W
UInt32 R/W R/W R/W
UInt64 R/W R/W R/W
Float R/W R/W R/W
Double R/W R/W R/W
String R/W R/W R/W
Boolean R/W R/W R/W
DateTime R/W R/W R/W
Guid R R R
ByteString R R R
XmlElement R R R
NodeId R R R
ExpandedNodeId R R R
StatusCode R R R
QualifiedName R R R
LocalizedText R R R
ExtensionObject R R R
DataValue R R R
Variant R R R
Number R/W R/W R/W
Integer R/W R/W R/W
UInteger R/W R/W R/W
Enumeration R/W R/W R/W
One-dimensional array R/W R/W R/W