Common OPC UA Server Test Report
We use the following common OPC UA Server and test the communication between it and the OPC UA driver in WAGO SCADA.
OPC UA Server
- Prosys: v5.5.0-341
- Softing: v1.46.0.7478
- Matrikon: v1.9.0.8629
Test Results
1. Supports connectivity via secure connections
| Authentication | Secured Connection |
| Prosys | Y | Y |
| Softing | Y | Y |
| Matrikon | Y | Y |
2. WAGO SCADA supports the following data types for OPC UA Server
| Prosys | Softing | Matrikon |
| Byte | R/W | R/W | R/W |
| SByte | R/W | R/W | R/W |
| Int16 | R/W | R/W | R/W |
| Int32 | R/W | R/W | R/W |
| Int64 | R/W | R/W | R/W |
| UInt16 | R/W | R/W | R/W |
| UInt32 | R/W | R/W | R/W |
| UInt64 | R/W | R/W | R/W |
| Float | R/W | R/W | R/W |
| Double | R/W | R/W | R/W |
| String | R/W | R/W | R/W |
| Boolean | R/W | R/W | R/W |
| DateTime | R/W | R/W | R/W |
| Guid | R | R | R |
| ByteString | R | R | R |
| XmlElement | R | R | R |
| NodeId | R | R | R |
| ExpandedNodeId | R | R | R |
| StatusCode | R | R | R |
| QualifiedName | R | R | R |
| LocalizedText | R | R | R |
| ExtensionObject | R | R | R |
| DataValue | R | R | R |
| Variant | R | R | R |
| Number | R/W | R/W | R/W |
| Integer | R/W | R/W | R/W |
| UInteger | R/W | R/W | R/W |
| Enumeration | R/W | R/W | R/W |
| One-dimensional array | R/W | R/W | R/W |